Single Compression Glands (SIBG series)
- Pass the compression nut (Pt.1), Washer No.1 (Pt.3) in succession order over the cable before commencing to strip the cable.
- Remove the outer sheath to the desired length depending on the length of leads required .Pass the rubber ring(Pt.4) over the armouring upto the outer sheath .
- Pass the 2nd washer (Pt. 5) over the armouring and splay out the armour wire one by one and then cut the armour wires according to the sizes of washer Pass the third washer (Pt .6). File the sharp edges of armour wires and bend them so that the armour wires are now secure between the two washers.
- Push the assembly through gland body (Pt.2) and tighten the compression nut. While doing so the rubber ring will expand in radial direction and will grip the cable. This will also ensure dust proof entry of the cable